ASCO Series 300 Manual Transfer Switch
An ASCO Series 300 manual transfer switch is the switch that lets you land a portable or rental generator when the permanent generator is down. It sits between the permanent generator and the facility automatic transfer switch. The permanent generator feeds one source. The portable generator feeds the other. The load side goes to the emergency input of the automatic transfer switch.
That is the only reason most commercial jobs buy this switch. It is the backup for the backup.
What NEC 700.3 Requires
NEC 700.3(F) applies when an emergency system has a single alternate source, usually the permanent on-site generator. While that generator is out for maintenance or repair, the code requires a permanent means to connect a portable or temporary generator. The connection cannot require cutting into the building wiring. The two sources cannot be tied together. Phase rotation must be marked. Transfer still has to meet 700.12.
How the Manual Transfer Switch Does the Job
The permanent generator output runs into one source of the manual transfer switch. The load side of the manual transfer switch runs to the emergency input of the facility automatic transfer switch. The other source of the manual transfer switch is the portable generator connection.
In normal operation the manual switch stays on the permanent generator. The automatic transfer switch does its usual job. When the permanent generator must come out of service, an operator moves the manual transfer switch to the portable-generator source. The automatic transfer switch still sees an emergency source. The portable set can carry the load. When the permanent generator returns, the operator moves the manual switch back.
The switch is a three-position, center-off design. It cannot close both sources at the same time. It can be locked in any position. Solid or switched neutral is available.
Two Ways to Land the Portable Generator
The portable side of the manual transfer switch can be left as bare lugs, and maintenance personnel land cables in the field when a portable generator is onsite
Or it can be ordered with an ASCO quick-connect panel. That puts Series 16 Cam-Lok connectors on the portable side so a rental generator lands with standard cam-lock cables. Big Lake Supply stocks common ASCO Series 300 quick connect input panels and can pair one with the manual transfer switch.
ASCO also builds the manual transfer switch with the Cam-Loks already in the same cabinet (MTQ, MUQ, MGQ, MPQ, and the dual-purpose MTDQ / MGDQ versions). Those are factory-integrated units. We quote them the same way we quote a stand-alone switch.
When This Is the Right Product
Use the Series 300 manual transfer switch when the building already has an automatic transfer switch and a permanent generator, and the job has to meet 700.3(F).
Use a dual-purpose quick connect panel with Kirk-key interlocks when the design calls for both a portable-generator connection and a load-bank connection in one cabinet, and the interlock is handled at the panel.
Use a Series 7000 bypass-isolation automatic transfer switch when the facility cannot take an outage to maintain the automatic transfer switch itself. That is a different problem. The manual transfer switch does not replace the ATS.
What We Stock and What We Quote
Big Lake Supply stocks a variety of ASCO Series 300 manual transfer switches. Availability changes. Contact us for current stock, price, and lead time.
Send the ampacity, voltage, poles, neutral arrangement (solid or switched), enclosure (Type 1 or Type 3R), and whether you want bare lugs or a quick-connect panel on the portable side. We will match a stocked switch or quote the unit with the Cam-Loks.