The ASCO Series 300G is the most advanced production AUTOMATIC transfer switch in the world.
The ASCO series 300G has the programmability to meet the most advanced mission critical applications. With features like event logging, power measurement, and advanced communications, its easy to not only be in control of your power system, you can be informed as well.
Communications is something that customers ask for almost every day, and with the ASCO series 300G you can stay informed anywhere, any time. When there is a power related event you can receive an e-mail, or a text message, or both. The days of wondering, and worrying about your facilities power are gone forever. The ASCO Series 300G even has its own web page so that you can check on the status ofyour power system from your smart phone, or tablet.



CONTROL AND DISPLAY PANEL
Easy to navigate 128x64 graphical LCD display with keypad provides LED indicators for switch position, source availability, not in auto, and alert condition.
STANDARD FEATURES
Inphase monitor to transfer motor loads, without any intentional off time, to prevent inrush currents from exceeding normal starting levels.
Engine exerciser to automatically test backup generator each week—with or without load for 20 minutes.
Selective load disconnect control contacts (two provided) which operate with time delay prior to and/or after load transfer and re-transfer.
60Hz or 50Hz selectable switch. Three – phase/single - phase selectable switch.
VOLTAGE & FREQUENCY SENSING
Three phase under and over voltage settings on normal and emergency sources.
Under and over frequency settings on normal and emergency sources.
True RMS Voltage Sensing with +/-1% accuracy Frequency Sensing Accuracy is +/- 0.1Hz
Voltage and Frequency parameters adjustable in 1% increments
Selecting settings : single or three phase voltage sensing on normal, and single phase sensing on emergency; 50 or 60 Hz
COMMUNICATIONS FEATURES
Requires accessory 72EE
Built in web server, with full display and control capabilities
E-mail capability for system events, including e-mail to SMS text messaging.
REMOTE CONTROL FEATURES
External Inputs for connecting:
Remote test switch.
Remote contact for test or for peak shaving applications. If emergency source fails, switch will automatically transfer back to normal source if acceptable.
Inhibit transfer to emergency
Remote time delay bypass switch emergency to normal
TIME DELAYS
Engine start time delay – delays engine starting signal to override momentary normal source outages – adjustable to 0 to 6 seconds (Feature 1C)
Transfer to emergency time delay – adjustable 0 to 60 minutes (Feature 2B)
Emergency source stabilization time delay to ignore momentary transients during initial generator set loading – adjustable 0 to 4 seconds (Feature 1F)
Re-transfer to normal time delay – adjustable 0 to 10 hours (Feature 3A)
Unloaded running time delay for engine cool down – adjustable 0 to 60 minutes (Feature 2E)
Pre and post signal time delay for selective load disconnect with a programmable bypass on source failures – adjustable0 to 5 minutes (specify ASCO Optional accessory 31Z)
Adjustable time delay to override momentary normal source outages to delay all transfer switch and engine-starting signals.